Online UPS Green Star Series 6K-10KVA
● Wide input voltage range (110-300 VAC).
● Emergency power off function (EPO)).
● 3-stage extendable charging design for optimized battery performance.
● Maintenance bypass available.
Key Features
- True double-conversion on line UPS.
- DSP technology guarantees high performance.
- Output power factor 0.8.
- Active input power factor correction 0.99.
- 50Hz/60Hz frequency converter mode.
- Standard backup UPS and long backup UPS in one integrated unit.
- Adjustable battery number from 16 pcs to 20 pcs.
- Adjustable charging current via LCD or software (0.5A~6A) .
- Wide input voltage range (110-300 VAC).
- Emergency power off function (EPO).
- 3-stage extendable charging design for optimized battery performance.
- Maintenance bypass available.
- SNMP/USB/RS-232 communications.
Technical Specification
MODEL
G6K (L)
G10K (L)
PHASE
1 phase in / 1 phase out
CAPACITY
6000 VA / 4800 W
10000 VA / 8000 W
INPUT
Nominal Voltage
208/220/230/240VAC
Voltage Range
Low Line Loss
110 VAC ± 3% at 50% Load
176 VAC ± 3% at 100% Load
Low Line Comeback
120 VAC ± 3% at 50% Load
186 VAC ± 3% at 100% Load
High Line Loss
300 VAC ± 3%
High Line Comeback
290 VAC ± 3%
Frequency Range
46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power Factor
≧ 0.99 @ 100% load
OUTPUT
Nominal Voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≦ 3 % THD (Linear Load),≦ 6 % THD (Non-linear Load)
Transfer Time
Bypass to Inverter(Line mode)
Zero
Inverter to Bypass(Line mode)
Zero
Waveform (Batt. Mode)
Pure Sine wave
EFFICIENCY
Line Mode
89%
90%
Battery Mode
88%
89%
BATTERY
Standard Model
Battery Type
12 V / 7 AH
12 V / 9 AH
Numbers
16
16
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current
Default:1.0 A ± 10%,
Default:1.0 A ± 10%,
Max.:2.0A ± 10%
Max.:2.0A ± 10%
Float Charging Voltage
218.4 VDC ± 1%
Long-run Model
Battery Type
Depending on applications
Numbers
16-20** (adjustable)
Charging Current
Default:4.0 A ± 10%,
Default:4.0 A ± 10%,
Max.:6.0A ± 10%
Max.:6.0A ± 10%
Float Charging Voltage
273 VDC ± 1% (based on 20 pcs batteries)
INDICATORS
LCD Panel
UPS status, Load level, Battery level,
Input/Output voltage,
Discharge timer, and Fault conditions
ALARM
Battery Mode
Sounding every 4 seconds
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Standard Model
Dimension,D*W*H (mm)
369*190*688
442*190*688
Net Weight (kgs)
60
75
Long-run Model
Dimension,D*W*H (mm)
369*190*318
442*190*318
Net Weight (kgs)
21
23
ENVIRONMENT
Operation Humidity
0-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 55dBA@1 Meter
Less than 58dBA@1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008,
Windows® 7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Specification is subject to change without further notice